低壓配電柜與配電箱安裝(zhuang)要考慮什么(me)標準
低(di)壓配(pei)電柜與配(pei)電箱(xiang)的安裝技術標準有(you)什么(me)?
低壓配電柜(ju)、配電箱、開關箱的殼(ke)體(BOX)原材料,一般(ban)采(cai)用厚鋼板,也可(ke)以采(cai)用絕緣層(insulated)板,但(dan)不適(shi)合(he)采(cai)用木制(zhi)原材料。
電(dian)源箱、開(kai)關箱應安裝擺正、堅固、不可顛(dian)倒、傾斜。移動式配電(dian)箱、開(kai)關箱的下底(di)與路面(mian)豎(shu)直實際應超過1.3
M、低于或是相當于1.5m;便(bian)攜式分配電(dian)箱(xiang)、開關箱(xiang)的下底與路面豎直的距離應大于0.6
M、不大于(yu)1.5m 。
進到低(di)壓配電(dian)柜的電(dian)源插頭,禁止用(yong)插頭聯接。
電(dian)源箱(xiang)(xiang)中間(jian)的距(ju)(ju)離不適合很遠。分配(pei)電(dian)箱(xiang)(xiang)與(yu)開關箱(xiang)(xiang)的距(ju)(ju)離不超(chao)出(chu)30m。開關箱(xiang)(xiang)與(yu)移(yi)動式用電(dian)量機器(qi)設備(equipment)的水準距(ju)(ju)離不適合超(chao)出(chu)3m。
每臺(tai)(tai)用(yong)電(dian)(dian)(dian)量機器(qi)設備(bei)(equipment)應(ying)有分別(bie)的型的開關箱。施工(gong)工(gong)地每臺(tai)(tai)用(yong)電(dian)(dian)(dian)量機器(qi)設備(bei)(equipment)應(ying)有分別(bie)型的開關箱,且務(wu)必考(kao)慮“一(yi)(yi)機一(yi)(yi)閘(zhá)一(yi)(yi)漏”規定(ding),禁止用(yong)同一(yi)(yi)個(ge)電(dian)(dian)(dian)器(qi)開關立即操(cao)縱(zong)(control)兩部及(ji)兩部左右用(yong)電(dian)(dian)(dian)量機器(qi)設備(bei)(equipment)(包括電(dian)(dian)(dian)源插座)。開關箱中務(wu)必設漏電(dian)(dian)(dian)保護開關,其額(e)定(ding)值走(zou)電(dian)(dian)(dian)姿(zi)勢(shi)電(dian)(dian)(dian)流量(Electron flow)應(ying)不超30ma,漏 電(dian)(dian)(dian)姿(zi)勢(shi)時間應(ying)不超0.1s。
低(di)壓配(pei)電柜、以便(bian)保(bao)證安全,全部配(pei)電箱(xiang)門應配(pei)鎖,不可在配(pei)電箱(xiang)和開(kai)關箱(xiang)內掛接或(huo)接插別的(de)臨電機器設備(equipment),開(kai)關箱(xiang)內禁止置放(fang)臟物。
配電(dian)箱(xiang)(柜(ju))的(de)外鍍(du)層(ceng)顏色應(ying)依據招標方的(de)規(gui)定開(kai)展靜電(dian)感(gan)應(ying)(是(shi)一種處在(zai)(zai)靜止不動情況(kuang)的(de)正電(dian)荷)靜電(dian)噴塑(su),鍍(du)層(ceng)應(ying)粘附堅固,顏色勻稱(cheng)(jūn yún),無皺褶、脫(tuo)落(luo)、黑斑、漏噴等安全隱(yin)患(huan),在(zai)(zai)距離(li)1Km觀查無顯著偏色和(he)返光,表(biao)層(ceng)整(zheng)平、整(zheng)潔,無凹痕(hen)、刮痕(hen)等損(sun)害(hai)狀況(kuang)。箱(xiang)(柜(ju))中應(ying)用的(de)別的(de)熱鍍(du)鋅(zinc)(galvanization)層(ceng)(zinc coat)的(de)零部件(jian),也應(ying)確(que)保 無脫(tuo)落(luo)、黑斑、鍍(du)漏、銹蝕等安全隱(yin)患(huan),表(biao)面的(de)品質必須做到上同樣規(gui)定。箱(xiang)(柜(ju))內不可有(you)臟物塵土(tu)等。