高低壓開關柜安裝時(shi)要留意哪(na)些?
高壓配電柜安裝時要留意哪些?
1.配電箱(盤)的設計標高(gao)或(huo)平整度超(chao)過容許誤差:是(shi)因為測量(liang)定(ding)位不或(huo)是(shi)是(shi)路面凹凸不平導致的,應立即開(kai)展調整。
2.配電箱鐵架子不華康:在(zai)安裝鐵架子以前(qian)未(wei)開展調直找正,或安裝時支撐點部位(wei)(position )偏位(wei)導致(zhi)的,運(yun)用(yong)拉(la)線(xian)再次找正后再開展固(gu)定(ding)不動。
3.配電箱股票盤(pan)面電具、儀表盤(pan)不堅固、整平或間(jian)隔不勻,壓(ya)(ya)頭不穩固、壓(ya)(ya)頭傷(shang)線(xian)(xian)芯,多(duo)芯輸電線(xian)(xian)壓(ya)(ya)頭未裝(zhuang)壓(ya)(ya)線(xian)(xian)端子(zi)。閘(zhá)具正下方未裝(zhuang)卡(ka)片(pian)框,螺絲太松(song)的應(ying)扭緊,間(jian)隔應(ying)按(an)規定調節勻稱(cheng)(jūn yún),找整平。傷(shang)線(xian)(xian)芯的一部分應(ying)剪去(cut off)重接,多(duo)芯線(xian)(xian)應(ying)安上壓(ya)(ya)線(xian)(xian)端子(zi),卡(ka)片(pian)框需補裝(zhuang)。
4.接(jie)地裝置輸電(dian)線(xian)(xian)橫(heng)截面不足(zu)或(huo)保護區線(xian)(xian)(又稱(cheng):避(bi)雷線(xian)(xian))橫(heng)截面不足(zu),保護區線(xian)(xian)(又稱(cheng):避(bi)雷線(xian)(xian))串連,對這種(zhong)不符合規(gui)定的應按相關要求開展改正(zheng)。配電(dian)箱、盤里的PE線(xian)(xian)端(duan)子適(shi)用一般公(gong)共工程建筑,民用型住房工程項目不適(shi)合應用。
5.盤后布線排(pai)序不齊整(zheng):應(ying)按環路(lu)捆扎整(zheng)束,并固定不動在(zai)盤里(li)。
6.配(pei)電箱(盤(pan))缺零(ling)(ling)部件,如合葉、鎖、螺絲等:應配(pei)全各種各樣安裝需要零(ling)(ling)部件。
7.鐵質箱電、氣割開(kai)長孔(kong):應(ying)(ying)一(yi)管一(yi)孔(kong),不運(yun)用電、氣割打孔(kong),管人箱應(ying)(ying)齊(qi)平。
8.配(pei)電箱(xiang)殼體(BOX)穩筑附(fu)近間隙過大:運用混凝(ning)土(原材料(liao):粉末(mo)狀膠凝(ning)材料(liao)無機物摻合(he)料(liao))水泥砂(sha)漿(jiang)將箱(xiang)、管(guan)筑實:堅固。
9.木(mu)箱包裝兩(liang)側無(wu)防腐蝕、內腔(qiang)不光滑:應按照規(gui)定解決。
10.配電箱鐵(tie)箱內腔點焊生銹:需補刷防腐漆(Antirust paint)。